        How to solve the high temperature of frequency converter and how to deal with the heat dissipation of frequency converter

        2023-05-20 12:11:07

        We know that the operating environment of the inverter is between - 10 ° C and + 50 ° C. The failure rate of frequency converter increases exponentially with the temperature. The service life decreases exponentially with the increase of temperature. It is reported that the service life of frequency converter will be halved when the ambient temperature is increased by 10 ℃. Therefore, we should pay attention to the problem of heat dissipation! When the frequency converter works, the current flowing through the frequency converter is very large, and the heat generated by the frequency converter is also very large, so the effect of its heat generation cannot be ignored. If the problem of converter heat dissipation is not handled well, it will affect the use state and service life of the converter, and even cause the damage of the converter.


        1、 Heat dissipation method of frequency converter:


        The heating of frequency converter is caused by internal loss. The main circuit accounts for 98% and the control circuit accounts for 2% in the loss of each part of the frequency converter. The data shows that the power consumption of the converter is generally 4~ 5% of its capacity. Among them, the inverter accounts for about 50%, the rectifier and DC circuit for about 40%, and the control and protection circuit for 5 ~ 15%. The 10C rule shows that when the temperature of the device decreases by 10 ° C, the reliability of the device will double. In order to ensure the normal and reliable operation of the frequency converter, it is necessary to deal with the heat dissipation of the frequency converter. The problem of converter heat dissipation is mainly the temperature and heat dissipation of converter working environment.


        For the heat dissipation method of frequency converter, it is generally divided into the following three types:


        1. Internal fan cooling


        The built-in fan is generally used for the general inverter with small capacity. Through the correct installation of the frequency converter, the heat dissipation capacity of the internal fan of the frequency converter can be maximized. The built-in fan can take away the heat inside the frequency converter. Heat is dissipated through the iron plate of the box where the frequency converter is located. The method of cooling only through the fan inside the frequency converter is applicable to the control box with a separate frequency converter and the control box with fewer control elements. If there are several inverters in the inverter control box, or other electrical components with large heat dissipation, the effect of heat dissipation is not very obvious.


        2. Fan cooling


        By adding several fans with air exchange and convection function in the control box where the frequency converter is installed, the heat dissipation effect of the frequency converter can be greatly improved and the temperature of the working environment of the frequency converter can be reduced. The capacity of the fan can be calculated by the heat dissipation of the frequency converter. Let's talk about general selection methods:


        According to our experience, the heat generated by the power consumption of every 1kW is calculated. The exhaust air volume of the fan is required to be 360m3 / h, while the power consumption of the frequency converter is 4-5% of its capacity. Here, we can calculate the relationship between the fan and its capacity as per 5%


        Exhaust air volume of fan (m3 / h): converter capacity x 5% * 360m3 / h / kw


        According to the above empirical formula, we can select fans for 90kw general inverter


        Exhaust air volume of fan (m3 / h): 90kw * 5% * 360m3 / h / kw


        Exhaust air volume of fan = 1620m3 / h


        Then select the models of fans from different manufacturers through the exhaust air volume of fans. Get fans that meet our conditions.


        Generally speaking, fan cooling is the main means of converter cooling at this stage. It is especially suitable for the large control cabinet, as well as the electrical components in the control cabinet working at the same time and heating at the same time. It is suitable for highly integrated centralized control cabinet and control box. And in recent years, due to the continuous progress of science and technology, the cooling fan is not as large as the previous years, small and powerful fans are everywhere. Cost performance is also much better than other ways of heat dissipation.


        3. Air conditioning cooling


        With the progress of science and technology, air conditioning is gradually applied to the production of control cabinet. And become one of the important means of heat dissipation. However, the frequency converter is rarely used for heat dissipation because of its high cost and relatively large volume. As the capacity of the general frequency converter ranges from several KVA to several + KVA, the capacity is not particularly large, so it is difficult to make the cost performance acceptable to the user. Only in special occasions (such as the special strict requirements on the working environment) and the frequency converter with a large capacity can be used This way. In addition, some of the air conditioners also involve the removal of waste water, so it is also necessary to consider more comprehensive in the process of panel cabinet complete set, increasing the design cost.


        In addition, there are other reasons to consider the heat dissipation effect of the frequency converter, such as high altitude (> 1000m), because of the decrease of air density, the heat dissipation capacity should be increased appropriately; there are also switching frequencies, the heat of the frequency converter mainly comes from IGBT (insulated gate bipolar crystal tube), and the heat of IGBT is concentrated in the moment of opening and closing. Therefore, when the switching frequency is high, the heating capacity of the frequency converter becomes larger.


        The fact shows that to deal with the heat dissipation of the frequency converter well requires not only the designer to do it from the frequency converter itself, but also the user to use it correctly and install it in strict accordance with the use instructions, with enough ventilation space and suitable use environment, and to maintain it regularly as much as possible, especially in the multi dust industries such as coal and carbon, to dust the use environment and the air duct of the frequency converter regularly, so as to Make the heat dissipation system of frequency converter play the normal function, make the temperature rise of frequency converter within the allowable value, the frequency converter can operate reliably, and bring greater economic and social benefits to the enterprise.


        2、 Daily inspection items of frequency converter:


        ① Whether the sound changes abnormally during the operation of the motor, including whether the vibration occurs during the operation of the motor.


        ② Whether the installation environment of frequency converter changes. If the ambient temperature is normal, the working temperature of the frequency converter is generally required to be within the range of - 10 ° C to + 40 ° C, preferably around 25 "C.


        ③ Whether the frequency converter cooling fan works normally, including whether the frequency converter cooling channel is unblocked. Whether the output current, voltage, frequency and other data of the inverter on the display panel are normal. Whether the characters on the display panel are clear and lack of strokes.


        ④ Whether the frequency converter is overheated. The infrared thermometer can be used to detect whether the radiator of the frequency converter is overheated or has peculiar smell. Check whether there is fault alarm display in the operation of frequency converter.


        ⑤ Regularly clean the filter screen of the air inlet in the electrical control cabinet. Keep the control cabinet and frequency converter in a good clean state at all times. Effectively remove the dust on the surface of the frequency converter to prevent the dust from entering the inverter. Especially metal dust. Effectively remove the oil contamination of the converter cooling fan.


        ⑥ Use the annual overhaul time to open the frequency converter, place the inspection in the interior that cannot be seen in normal daily operation, and carry out cleaning work. Use brush or vacuum cleaner to clean the circuit board of frequency converter, internal rectifier module, IGBT module, DC filter electrolytic capacitor, input and output reactor and other parts. The unqualified electronic components shall be replaced (Note: the internal filter electrolytic capacitor of frequency converter generally needs to be replaced in 4-5 years).


        ⑦ Check the cooling electric fan, which is easy to damage components. Its life is limited by bearings (it is an axial fan. According to the operation of frequency converter, the fan or fan bearing shall be replaced once every 2-3 years.


        General purpose frequency converter


        label

        QR code

        The public,

        Mobile station
        The public, Mobile station

        Contact

        未標題-8.png 0755-81719517
        未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
        未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

        Navigation

        Home          About

        Product      Case

        Solution      Service

        Job      News

        Contact          

        Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
        主站蜘蛛池模板: 久久亚洲精品人成综合网| 欧美人与动牲交A免费观看| 国产AV福利第一精品| 国产精品无码av一区二区三区| 色老99久久精品偷偷鲁| 国产线播放免费人成视频播放| 国产成人拍精品视频午夜网站| 成人无码午夜在线观看| 美女大bxxxxn内射| 国产伦精品一区二区三区| 永久免费AV无码网站YY| 亚洲中文字幕无码爆乳APP| 婷婷色香五月综合缴缴情香蕉| 国产精品久久中文字幕第一页| 精品一区二区三区不卡| 91精品国产三级在线观看| 日韩一区二区黄色一级片| 亚洲伊人精品久视频国产| 亚洲人成精品久久久久| 久久精品无码一区二区小草| 一本色道久久综合亚洲精品蜜臀| 欧美成本人视频免费播放| 国产成a人亚洲精v品无码| 国产成人亚洲精品自产在线| 中文成人无字幕乱码精品区| 曰韩无码二三区中文字幕| 伊人久久综合无码成人网| 日韩欧美一卡2卡3卡4卡无卡免费2020 | 精品国产中文字幕在线| 欧美成人怡春院在线激情| 无码激情亚洲一区| 久久国产精品亚洲精品99| 中文激情一区二区三区四区| 亚洲国产一区二区三区| 视频专区熟女人妻第二页| av色蜜桃一区二区三区| 亚洲精品国产自在现线最新 | 亚洲VA欧美VA国产综合| XXXXXHD亚洲日本HD| 精品一区二区不卡免费| 草草浮力影院|